1
DEH41552 INSTALLATION INSTRUCTION FOR RIGHT POLE MOUNTING ONLY
Undervoltage Release Device
CAUTION: The device is factory installed in the right
pole only. Before inspecting or beginning any maintenance
works on the breaker, it must be dis connected from all
voltage sources, both power and control, an d breaker
placed in th e off (open ).
NOTES:
1.A ny work r equiring cover removal of a sealed breaker
voids UL listing. The UL label must be destroyed.
2 . UVR cannot be installed in bre akers code dated with
this numb er or lower: 10 1
This accessory to be installed in Right Pole only.
ELECTRICAL DATA
Cat No.
(Right Pole Only)
TEYXU1
TEYXU2
TEYXU3
TEYXU4*
TEYXU6
TEYXU7
TEYXU8
TEYXU9*
*Rated UVR coils includes externally serious mounted
resistor.
D ESCRIPTION
T his device is used for automatic breaker tripping when
line voltage drops below a pre-determined level.
—
Figure 1.
MA Current
Rated
Voltage
Dc
Ac
24V Ac
---
100
48V Ac
---
120V Ac
---
240V Ac
---
24V Dc
100
48V Dc
50
125V Dc
18
250V Dc
11
STEP 1
Breaker Preparation for Field Installation.
Open breaker contacts by moving handle to the breaker
"OFF" position as shown in Figure 2.
50
STEP 2
Removing Cover
17
10
Remove breaker c over by re moving cover screws as shown
in Figure 3. Tar must be removed and discarded to gain
---
access to screw. Remove and save plastic handle and
---
shutter.
Push trip bar towards load end to trip mechanism.
---
---
—
Fig ure 2.
—
Figure 3.