Huawei FusionModule500 Product Description
Huawei FusionModule500 Product Description

Huawei FusionModule500 Product Description

Smart mini data center
Hide thumbs Also See for FusionModule500:

Advertisement

Quick Links

FusionModule500 Smart Mini Data Center
Product Description (ECC800e)
Issue
05
Date
2019-11-22
HUAWEI TECHNOLOGIES CO., LTD.

Advertisement

Table of Contents
loading

Summary of Contents for Huawei FusionModule500

  • Page 1 FusionModule500 Smart Mini Data Center Product Description (ECC800e) Issue Date 2019-11-22 HUAWEI TECHNOLOGIES CO., LTD.
  • Page 2 Notice The purchased products, services and features are stipulated by the contract made between Huawei and the customer. All or part of the products, services and features described in this document may not be within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements, information, and recommendations in this document are provided "AS IS"...
  • Page 3: About This Document

    Product Description (ECC800e) About This Document About This Document Purpose This document describes the FusionModule500 Smart Mini Data Center (smart module for short) in terms of the appearance, features, and specifications for you to understand the product information. Intended Audience This document is intended for: ...
  • Page 4 FusionModule500 Smart Mini Data Center Product Description (ECC800e) About This Document Symbol Description Supplements the important information in the main text. NOTE is used to address information not related to personal injury, equipment damage, and environment deterioration. Change History Changes between document issues are cumulative. The latest document issue contains all updates made in previous issues.
  • Page 5: Table Of Contents

    FusionModule500 Smart Mini Data Center Product Description (ECC800e) Contents Contents About This Document ........................ii 1 Overview ............................1 1.1 Positioning ..................................1 1.2 Features ..................................3 2 Typical Application Scenarios and Configurations ............... 5 2.1 Typical Scenarios ................................5 2.2 Typical Configuration (Single-Phase 220 V Power System) ..................
  • Page 6 FusionModule500 Smart Mini Data Center Product Description (ECC800e) Contents 3.4.4 Smoke Detector ............................... 42 3.4.5 T/H Sensor ................................44 3.4.6 Door Status Switch ..............................45 3.4.7 (Optional) Intelligent Battery Monitoring System ....................45 3.4.7.1 CIM ..................................46 3.4.7.2 BIM ..................................56 3.4.8 Water Sensor ................................
  • Page 7: Overview

    1.1 Positioning To meet the requirements for customers' growing services, Huawei launches the FusionModule500 that can be rapidly deployed and flexibly expanded. The FusionModule500 is positioned as a smart module solution and occupies about 10 m . It is mainly used in the equipment rooms of county-level governments, bank business outlets, and small and medium-sized enterprises.
  • Page 8 FusionModule500 Smart Mini Data Center Product Description (ECC800e) 1 Overview Figure 1-1 Position of the FusionModule500 in the financial industry (1) FusionModule5000 (2) FusionModule2000 (3) FusionModule800 (4) FusionModule500 Issue 05 (2019-11-22) Copyright © Huawei Technologies Co., Ltd.
  • Page 9: Features

    FusionModule500 Smart Mini Data Center Product Description (ECC800e) 1 Overview Figure 1-2 Position of the FusionModule500 for governments (1) FusionModule5000 (2) FusionModule2000 (3) FusionModule800 (4) FusionModule500 1.2 Features Integration The smart module integrates the cabinets, power supply and distribution system, and monitoring system to provide a comprehensive solution.
  • Page 10 FusionModule500 Smart Mini Data Center Product Description (ECC800e) 1 Overview Safety and Reliability  The Converged Cabinet incorporates the UPS, monitoring system, and power distribution system that are designed in modular manner and feature high security and reliability.  The powerful monitoring system allows you to master the infrastructure status anytime and improves the protection capability of cabinets.
  • Page 11: Typical Application Scenarios And Configurations

    FusionModule500 Smart Mini Data Center Product Description (ECC800e) 2 Typical Application Scenarios and Configurations Typical Application Scenarios and Configurations 2.1 Typical Scenarios The smart module is mainly used in the equipment rooms of bank business outlets, small and medium-sized enterprises, and governments.
  • Page 12: Typical Configuration (Single-Phase 220 V Power System)

    FusionModule500 Smart Mini Data Center Product Description (ECC800e) 2 Typical Application Scenarios and Configurations 2.2 Typical Configuration (Single-Phase 220 V Power System) Single-Cabinet Solution Figure 2-1 24 U Converged Cabinet Table 2-1 Typical configuration 1 Item Specifications Cabinet dimensions (W x D x H)
  • Page 13 FusionModule500 Smart Mini Data Center Product Description (ECC800e) 2 Typical Application Scenarios and Configurations Figure 2-2 42 U Converged Cabinet Table 2-2 Typical configuration 2 Item Specifications Cabinet dimensions (W x D x H) 600 mm x 1100 mm x 2000 mm Power backup time 15–240 minutes...
  • Page 14 FusionModule500 Smart Mini Data Center Product Description (ECC800e) 2 Typical Application Scenarios and Configurations Two-Cabinet Solution Figure 2-3 Converged Cabinet + battery cabinet Table 2-3 Typical configuration 3 Item Specifications Cabinet dimensions (W x D x H) 600 mm x 1100 mm x 2000 mm Power backup time 15–240 minutes...
  • Page 15 FusionModule500 Smart Mini Data Center Product Description (ECC800e) 2 Typical Application Scenarios and Configurations Figure 2-4 Converged cabinet + network cabinet Table 2-4 Typical configuration 4 Item Specifications Cabinet dimensions (W x D x H) 600 mm x 1100 mm x 2000 mm...
  • Page 16 FusionModule500 Smart Mini Data Center Product Description (ECC800e) 2 Typical Application Scenarios and Configurations Three-Cabinet Solution Figure 2-5 Network cabinet + converged cabinet + battery cabinet Table 2-5 Typical configuration 5 Item Specifications Cabinet dimensions (W x D x H)
  • Page 17 FusionModule500 Smart Mini Data Center Product Description (ECC800e) 2 Typical Application Scenarios and Configurations Item Specifications Monitoring ECC800e, T/H sensor (Converged Cabinet), T/H sensor (network cabinet, optional), camera (optional), VCN (optional), door status sensor (Converged Cabinet), door status sensor (network...
  • Page 18 FusionModule500 Smart Mini Data Center Product Description (ECC800e) 2 Typical Application Scenarios and Configurations Table 2-6 Typical configuration 6 Item Specifications Cabinet dimensions (W x D x H) 600 mm x 1100 mm x 2000 mm NOTE Network cabinet dimensions (W x D x H):...
  • Page 19: Typical Configuration (Dual-Live Wire 208 V Power System)

    FusionModule500 Smart Mini Data Center Product Description (ECC800e) 2 Typical Application Scenarios and Configurations 2.3 Typical Configuration (Dual-Live Wire 208 V Power System) Single-Cabinet Solution Figure 2-7 42 U Converged Cabinet Table 2-7 Typical configuration 1 Item Specifications Cabinet dimensions (W x D x H)
  • Page 20 FusionModule500 Smart Mini Data Center Product Description (ECC800e) 2 Typical Application Scenarios and Configurations Two-Cabinet Solution Figure 2-8 Converged Cabinet + battery cabinet Table 2-8 Typical configuration 2 Item Specifications Cabinet dimensions (W x D x H) 600 mm x 1100 mm x 2000 mm Power backup time 15–240 minutes...
  • Page 21 FusionModule500 Smart Mini Data Center Product Description (ECC800e) 2 Typical Application Scenarios and Configurations Item Specifications Monitoring ECC800e, T/H sensor, camera (optional), VCN (optional), door status sensor (Converged Cabinet), door status sensor (battery cabinet, optional), smoke detector, water sensor, pad (optional), WiFi converter...
  • Page 22 FusionModule500 Smart Mini Data Center Product Description (ECC800e) 2 Typical Application Scenarios and Configurations Item Specifications Power backup time 15–240 minutes Power distribution UPS2000-G, PDU5000, rPDU, battery pack (optional)/external battery (optional), and transformer Monitoring ECC800e, T/H sensor (Converged Cabinet), T/H...
  • Page 23 FusionModule500 Smart Mini Data Center Product Description (ECC800e) 2 Typical Application Scenarios and Configurations Table 2-10 Typical configuration 4 Item Specifications Cabinet dimensions (W x D x H) 600 mm x 1100 mm x 2000 mm NOTE Network cabinet dimensions (W x D x H):...
  • Page 24 FusionModule500 Smart Mini Data Center Product Description (ECC800e) 2 Typical Application Scenarios and Configurations Four-Cabinet Solution Figure 2-11 Network cabinet + Converged Cabinet + battery cabinet + battery cabinet Table 2-11 Typical configuration 5 Item Specifications Cabinet dimensions (W x D x H)
  • Page 25 FusionModule500 Smart Mini Data Center Product Description (ECC800e) 2 Typical Application Scenarios and Configurations Item Specifications Monitoring ECC800e, T/H sensor (Converged Cabinet), T/H sensor (network cabinet, optional), camera (optional), VCN (optional), door status sensor (Converged Cabinet), door status sensor (network cabinet, optional), door...
  • Page 26: System Architecture

    FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture System Architecture 3.1 Structural System The smart module houses the battery cabinet, Converged Cabinet, and network cabinet, and employs air channels before and after cabinets. The cabinet possesses the following features: ...
  • Page 27: Power Supply And Distribution System

    FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture Item Specifications (42 U) Specifications (24 U) Installation mode Installed on a concrete floor Installed on a concrete floor or electrostatic discharge or ESD floor (ESD) floor Static load...
  • Page 28 FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture Figure 3-2 Power distribution conceptual diagram for the 220 V single-phase scenario with the 6 kVA/10 kVA UPS The power distribution system meets the power supply requirements of single-phase 220 V/230 V/240 V.
  • Page 29: Kva Ups

    FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture Item Specifications (10 Specifications (6 Specifications (3 kVA UPS) kVA UPS) kVA UPS) UPS backup power Battery pack Battery pack Battery pack (optional): (optional): (optional):    0–4 (7 Ah/240...
  • Page 30: Kva Ups

    FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture Item Specifications Maximum input current 19 A Number of phases Input power factor (full load) > 0.99 input frequency Rated frequency: 50 Hz/60 Hz Range: 40–70 Hz Total distortion of the input current <...
  • Page 31: Kva Ups

    FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture Table 3-4 6 kVA UPS technical specifications Item Specifications Rated capacity 6 kVA Maximum input current 32 A Number of phases Input power factor (full load) > 0.99 input frequency Rated frequency: 50 Hz/60 Hz Range: 40–70 Hz...
  • Page 32: Pdu5000

    FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture Table 3-5 10 kVA UPS technical specifications Item Specifications Rated capacity 10 kVA Maximum input current 50 A Number of phases Input power factor (full load) > 0.99 input frequency Rated frequency: 50 Hz/60 Hz Range: 40–70 Hz...
  • Page 33: Rpdu

    FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture Table 3-6 PDU5000 technical specifications Item Specifications (3 kVA Specifications (6 kVA UPS) UPS/10 kVA UPS) Maximum input current 32 A 63 A Number of phases input frequency 50 Hz/60 Hz...
  • Page 34: Dual-Live Wire 208 V Power System

    FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture Item Specifications Specifications Specifications (Vertically (Vertically (Horizontally Installed Installed Installed 1 U Full-Height Half-Height rPDU) rPDU) rPDU) Output port IEC: 20 x C13 + 4 x IEC: 9 x C13 + 3 x...
  • Page 35: Kva Ups

    FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture Item Specifications (10 kVA Specifications (6 kVA UPS) UPS) UPS backup power Battery pack (optional): Battery pack (optional):   0–3 (7 Ah/240 V) 0–3 (7 Ah/240 V) ...
  • Page 36: Kva Ups

    FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture Item Specifications Output voltage 208 V Tolerance: ± 1% Output frequency  Normal mode: 50 Hz/60 Hz (± 6 Hz)  Battery mode: 50 Hz/60 Hz (± 0.05%) Output power factor...
  • Page 37: Pdu5000

    FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture Item Specifications Output voltage 208 V Tolerance: ± 1% Output frequency  Normal mode: 50 Hz/60 Hz (± 6 Hz)  Battery mode: 50 Hz/60 Hz (± 0.05%) Output power factor Efficiency 94.5%...
  • Page 38: Rpdu

    FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture Item Specifications UPS output 2-pole 63 A circuit breaker UPS maintenance bypass 2-pole 63 A circuit breaker Output branch Four 1-pole 40 A circuit breakers and one 1-pole 16 A circuit breakers...
  • Page 39: Battery Cabinet

    FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture Figure 3-11 Battery pack Table 3-13 Battery pack technical specifications Item Specifications (7 Ah/240 V) Specifications (9 Ah/240 V) Capacity (single 7 Ah 9 Ah battery pack) Voltage (single...
  • Page 40 FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture Figure 3-12 Battery cabinet Figure 3-13 Battery cabinet components (1) Circuit breaker (2) BIM (3) Batteries (4) BIB (5) CIM Issue 05 (2019-11-22) Copyright © Huawei Technologies Co., Ltd.
  • Page 41 FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture Table 3-14 Battery cabinet technical specifications Item Specifications Dimensions (H x W x D) 2000 mm x 600 mm x 1100 mm Color Black Material High-intensity class A carbon cold rolled steel plate and...
  • Page 42: Cooling System

    FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture Battery Specifications Layer (from Top to Bottom) Number of Batteries Layer 3 Layer 4 65 Ah/100 Ah Layer 1 Layer 2 Layer 3 Layer 4 3.3 Cooling System The cooling system is deployed by customers by default. Civil smart cooling products can be configured to cool equipment based on the equipment room temperature.
  • Page 43: Ecc800E

    FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture Figure 3-14 System network diagram 3.4.2 ECC800e The ECC800e monitors the equipment and environment inside the smart module. The ECC800e supports alarm notification by SMS and email, enabling remote maintenance. Information about a maximum of 20 users who will receive alarm notification can be displayed.
  • Page 44 FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture Table 3-17 Technical specifications Item Specification Power Input  Supports one AC input.  Rated operating voltage: 100-240 V AC.  Rated operating frequency: 50 Hz/60 Hz.  Input current: MAX0.5 A.
  • Page 45 FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture Table 3-18 Indicators on the ECC800e main control module Indicator Color Name Status Description Green Module running Steady on The power supply is normal, status indicator the program is being loaded, or WiFi WPS is pairing.
  • Page 46: Optional) Independent Deployment Ai/Di Unit

    FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture Table 3-19 Wireless network pairing and IP address reset buttons Name Function Function Description Status 1. When the system WiFi pairing button Reserve enters the pairing mode, the RUN indicator is steady on.
  • Page 47 FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture Table 3-20 Indicators on the front panel of the independent deployment AI/DI unit Silk Screen Color Meaning Status Description The power Green Power indicator Steady on supply is normal.
  • Page 48: Smoke Detector

    FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture Silk Screen Port Description AI/DI_1 to Provide 12 V DC outputs for sensors and are compatible with 4 mA to AI/DI_8 20 mA current signals, signals from current-based smoke sensors and water sensors, dry contact signals, and NTC signals.
  • Page 49 FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture Figure 3-17 Smoke detector Table 3-23 Smoke detector technical specifications Item Specifications Operating voltage 9–27 V Alarm current < 20 mA Indication Monitoring: The red indicator blinks once every 3 to 8 seconds.
  • Page 50: T/H Sensor

    FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture 3.4.5 T/H Sensor Figure 3-18 T/H sensor Table 3-24 T/H sensor technical specifications Item Specifications –20° C to +70° C Temperature measurement range Temperature measurement precision ± 1° C (at 25° C) –10°...
  • Page 51: Door Status Switch

    FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture 3.4.6 Door Status Switch Figure 3-19 Door status switch Table 3-26 Door status switch technical specifications Item Specifications Connection method Using wiring terminals Rated current 500 mA 25 mm ≤ Opening distance ≤ 45 mm...
  • Page 52: Cim

    FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture The battery interface module (BIM) is a battery monitoring module that monitors the voltages, internal resistances, and pole temperatures of batteries.  One CIM can support a maximum of 300 BIMs, and manage BIMs of a maximum of four battery strings.
  • Page 53 FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture Appearance Figure 3-21 Figure 3-22 show the appearance of a CIM. Figure 3-21 CIM front view (1) –48 V 0.5 A port (power (2) PoE port (3) COM_IN port (RS485...
  • Page 54 FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture Figure 3-22 CIM bottom view (1) Fastener (2) Micro SD card slot (3) Default button (IP (4) ADDR dual in-line package (DIP) switch (RS485 reset) communications address) (5) 12V 2A port (power...
  • Page 55 FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture Table 3-28 –48 V, 0.5 A port pin definitions Definition Description The system provides 48 V DC operating voltage in this – scenario. PoE Port Figure 3-24 PoE port pins...
  • Page 56 FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture COM Port Figure 3-25 COM port pins Table 3-30 COM port pin definitions Signal Description RS485+ Two cascaded RS485 communication ports RS485– RS485+ RS485– DI and DO Ports Table 3-31 DI and DO port pin definitions...
  • Page 57 FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture Definition Signal Status Description Initial Remarks Description Status output signal contact output is open.  Closed: The dry contact output is closed. Current Monitoring Port Figure 3-26 Current monitoring port pins...
  • Page 58 FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture BCB Port Figure 3-27 BCB port pins Table 3-33 BCB_1–BCB_4 port pin definitions Definition Signal Status Description Initial Status Remarks Description Monitors whether  Grounded: BCB The four BCBs...
  • Page 59 FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture Definition BCB_IN BCB_OUT Status Initial Status Description Signal Signal Description Description Description port cascading Signal output Monitors  Grounded: Disconnected management. port for the whether the The battery battery circuit...
  • Page 60 FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture Table 3-36 Indicator description Indicator Color Meaning Status Description Measure Wireless No network Requires no RF_Z Green Steady on communication parameters exist. handling. status (A network is to be created.)
  • Page 61 FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture Indicator Color Meaning Status Description Measure Alarm indicator Steady on The actual number Check the value of online devices of BIM number, is less than the the BIM cable...
  • Page 62: Bim

    FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture Default Button Table 3-38 Default button description Name Definition Function Default button Hold down the button Reset to the default IP address for more than 10 (192.168.0.10) seconds. 3.4.7.2 BIM The BIM is a battery monitoring module that monitors the voltages, internal resistances, and pole temperatures of batteries and supports 12 V power.
  • Page 63: Water Sensor

    FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture Indicator Color Silk Status Description Screen Blinking at The networking has started but not super short completed. intervals Blinking at The networking succeeds. long intervals Alarm The BIM is not faulty.
  • Page 64: Optional) Pad

    FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture Figure 3-29 Water sensor Table 3-41 Water sensor technical specifications Item Specifications Operating voltage 12 V DC (9–16 V DC) Insulation resistance > 500 megohms –20° C to +70° C, 10%–80% RH...
  • Page 65: Optional) Wifi Converter

    FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture Table 3-42 Pad technical specifications Item Specifications Dimensions (L x W x 248.5 mm x 150 mm x 8.3 mm Weight About 433 g Touchscreen 9.6-inch, 1280x800 IPS full view, IPS screen, and capacitive...
  • Page 66: Optional) Vcn540

    FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture Table 3-43 WiFi converter technical specifications Item Specifications IEEE 802.11n, IEEE 802.11g, and IEEE Wireless standard 802.11b Network bandwidth  11n: up to 150 Mbit/s  11g: up to 54 Mbit/s ...
  • Page 67: Optional) Ip Camera

    FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture Item Description Video forwarding Supports a maximum of 128 video forwarding channels or 320 Mbit/s video forwarding bandwidth. Supports a maximum of 32 video playback Video playback and download and download channels or 320 Mbit/s video playback and download bandwidth.
  • Page 68: Optional) Gsm Modem

    FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture Figure 3-33 IPC6325 camera Table 3-46 IPC6325 camera technical specifications Item Specifications Image sensor 1/2.7'' two-megapixel progressive scan CMOS  Lowest illuminance Color: 0.01 Lux (F1.4, AGC ON) ...
  • Page 69: Optional) Infrared Remote Control Module

    FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture Table 3-47 GSM modem technical specifications Item Specifications Power voltage 4.75–5.25 V (recommended value: 5 V) –20° C to +55° C Operating temperature –40° C to +70° C Storage temperature...
  • Page 70: Cable Management

    FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture Table 3-48 Technical specifications for the infrared remote control module Item Specifications Number of supported remote control 4 (maximum) commands Communication Interworks with the monitoring system over Modbus-RTU to implement remote control.
  • Page 71 FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture Figure 3-35 Cable manager Table 3-49 Cable manager specifications Dimensions (H x W x D) Weight Space Occupied 43.6 mm x 482.6 mm x 91 mm 0.56 kg Cable Ring A cable ring is installed on a side post in the cabinet to secure vertically routed cables.
  • Page 72 FusionModule500 Smart Mini Data Center Product Description (ECC800e) 3 System Architecture Table 3-50 Cable ring specifications Name Dimensions (H x W x D) Weight Standard cable ring 55 mm x 48 mm x 188.6 mm 0.163 kg Small cable ring 55 mm x 48 mm x 44 mm 0.096 kg...
  • Page 73: A Technical Specifications (Single-Phase 220 V Power System)

    FusionModule500 Smart Mini Data Center A Technical Specifications (Single-Phase 220 V Power Product Description (ECC800e) System) Technical Specifications (Single-Phase 220 V Power System) Table A-1 Key technical specifications Item Specifications ≤ 2 (including the Converged Cabinet and Number of IT cabinets network cabinet) ≤...
  • Page 74: B Technical Specifications (Dual-Live Wire 208 V Power System)

    FusionModule500 Smart Mini Data Center B Technical Specifications (Dual–Live Wire 208 V Product Description (ECC800e) Power System) Technical Specifications (Dual–Live Wire 208 V Power System) Table B-1 Key technical specifications Item Specifications ≤ 2 (including the Converged Cabinet and Number of IT cabinets network cabinet) ≤...
  • Page 75: C Derating Coefficients

    FusionModule500 Smart Mini Data Center Product Description (ECC800e) C Derating Coefficients Derating Coefficients Table C-1 UPS2000-G derating coefficients Altitude (Unit: m) Derating Coefficient 1000 1500 0.95 2000 0.91 2500 0.86 3000 0.82 3500 0.78 4000 0.74 Coefficients in the previous table are based on the dry air density (sea level temperature + 15° C) of 1.225 kg/m...
  • Page 76: D Acronyms And Abbreviations

    FusionModule500 Smart Mini Data Center Product Description (ECC800e) D Acronyms and Abbreviations Acronyms and Abbreviations application Battery control I/O board Battery Interface Module Communication Interface Module energy control center power distribution unit uninterruptible power system virtual customer network Issue 05 (2019-11-22)