Page 1
DOC. N° 1SDH001000R0002 - L7804 SACE Emax 2 Emax low voltage air circuit-breakers E2.2-E4.2-E6.2 Installation, operation maintenance instructions for the installer and the user...
All the remaining operations described in the handbook must be performed by expert persons, in the electrical area. ABB declines all liability for damage to persons or property caused by failure to comply with the instructions in this document.
• these warnings and alarms do not include all conceivable ways to make installation, use and maintenance recommended by ABB or not, that may be made, or possible consequences and complications of each conceivable way, nor shall ABB investigate all those ways.
If there is any damage to the packaging upon receipt and / or inconsistencies between order Report and product identification label or product please contact ABB. Damage to the packaging must be reported no later than seven days from receipt of the material.
Mounting anti-racking locks Before installing the fixed part, it is necessary to fit the lock that prevents the insertion of circuit- breakers with different electrical characteristics from the fixed part. See Figure 50. Information on the assembly is available from the web site http://www.abb.com/abblibrary/ DownloadCenter/, in particular with the kit sheet 1SDH001000R0701.
Fix the fixed part to a horizontal surface using four M8 x 25 screws for E2.2 and E4.2 fixed withdrawable circuit-breaker. parts, and using six M8 x 25 screws for E6.2 fixed parts. The screws are supplied by ABB. See Figure 51. Tighten the screws with tightening torque = 30 Nm.
DownloadCenter/, in particular with the Emax 2 catalogue 1SDC200023D0201. Dimensions Information on the overall dimensions is available on the web site http://www.abb.com/ abblibrary/DownloadCenter/, in particular with the Emax 2 catalogue 1SDC200023D0201.
Select the Trip Test command Check that the CB opens and that the TU Reset button comes out Further information on Ekip Connect is available from the web site http://www.abb.com/ abblibrary/DownloadCenter/, in particular with the manual 1SDH000891R0002. Ekip Dip protection release | 4 - Test...
Iinst The purpose of this protection is to maintain the integrity of the circuit-breaker and installation in the case of particularly high current values requiring shorter reaction times than those provided by the instantaneous short-circuit-protection. The protection cannot be disabled, and the tripping threshold and time are defined by ABB. Additional functions Functions...
W2 (LOCAL BUS) * A), * I) Diagrams 32 Further information is available on page 156, or on the site http://www.abb.com/abblibrary/ DownloadCenter/, where the wiring diagram is available 1SDM000091R0001. Signallings The following table illustrates the possible signals, and their meaning: Pos.
O SC SYNC * L), * M) Diagram 48 Further information is available on page 156, or on the site http://www.abb.com/abblibrary/ DownloadCenter/, where the wiring diagram is available 1SDM000091R0001. Signallings The following table illustrates the possible signals, and their meaning: Pos.
* L), * M) * L), * M) Diagrams 41 - 42 - 43 Further information is available on page 156, or on the site http://www.abb.com/abblibrary/ DownloadCenter/, where the wiring diagram is available 1SDM000091R0001. Electronic accessories | 5 - Ekip Signalling 2K modules...
* L), * M) Diagrams 53 - 63 Further information is available on page 156, or on the site http://www.abb.com/abblibrary/ DownloadCenter/, where the wiring diagram is available 1SDM000091R0001. Termination resistors The modules provide the possibility to insert a 220 Ω termination resistor on the RS-485 bus, by setting the dip-switches Rterm on the side of the modules, in position on.
* L), * M) Diagrams 55 - 65 Further information is available on page 156, or on the site http://www.abb.com/abblibrary/ DownloadCenter/, where the wiring diagram is available 1SDM000091R0001. Termination resistor The modules provide the possibility to insert a 120 Ω termination resistor on the RS-485 bus, by setting the dip-switches Rterm on the side of the modules, in position on.
* L), * M) * L), * M) Diagrams 52 - 62 Further information is available on page 156, or on the site http://www.abb.com/abblibrary/ DownloadCenter/, where the wiring diagram is available 1SDM000091R0001. Electronic accessories | 9 - Ekip Com Modbus TCP modules...
TCP Client modules. MAC Address It is the address assigned by ABB, having a OUI equal to ac:d3:64 Organizationally Unique Identifier, formed from the first three bytes of a MAC address, and which uniquely identifies the manufacturer of an Ethernet device.
The information on the modules that can be displayed is as follows: • The serial number and the software version. • The MAC address, assigned by ABB and with an OUI (Organizationally Unique Identifier, formed of the first three bytes of a MAC address, and which uniquely identifies the manufacturer of an Ethernet device) equal to ac:d3:64.
Ethernet network with an ABB proprietary protocol. IMPORTANT: the module can only be connected to internal Ethernet networks with a single switchgear or multiple switchgears, to which releases or ABB Emax 2 accessories are collected. It is responsibility of the installer to make sure that all the necessary security measures are adopted for all the devices connected (for example, the necessary access authorizations).
Only with Ekip Dip releases, the module can also be used with a function similar to that one of the Ekip Com Modbus TCP module, but with possibility to communicate only with an ABB master (for example, Ekip Connect or Ekip Control Panel).
Gateway Address. MAC Address It is the address assigned by ABB, having a OUI equal to ac:d3:64 Organizationally Unique Identifier, formed from the first three bytes of a MAC address, and which uniquely identifies the manufacturer of an Ethernet device.
XB4 2 Diagrams 78 - 76 Further information is available on page 156, or on the site http://www.abb.com/abblibrary/ DownloadCenter/, where the wiring diagram is available 1SDM000091R0001. Compatibility Ekip Com Actuator module is supplied on request and is compatible with all Ekip releases if there is an Ekip Com or Ekip Link module present.
IMPORTANT: the RC toroid can be selected as an alternative to the Gext toroid. Therefore the RC and Gext protections are alternatives. Further information on the connection of the RC sensor is available at the site http://www.abb. com/abblibrary/DownloadCenter/, in particular in kit sheet 1SDH001000R0521.
ABB | SACE Emax 2 Ekip Connect application Ekip Connect is the free application for communication and testing of ABB low voltage circuit- breakers equipped with compatible releases, in particular Ekip releases. It must be installed on PCs equipped with the Microsoft Windows® operating system by downloading it from the site http://www.abb.com/abblibrary/DownloadCenter.
It includes a led that is green when the device is energized and the batteries are charged, and red when the batteries are drained and need to be replaced. Further information on Ekip TT is available from the web site http://www.abb.com/abblibrary/ DownloadCenter/, in particular on kit sheet 1SDH001000R0519, and in the Ekip Connect application manual 1SDH000891R0002.
Further information on the connection of the RC sensor is available at the site http://www.abb. com/abblibrary/DownloadCenter/, in particular in kit sheet 1SDH001000R0520. External neutral This is a current sensor for the neutral conductor outside the circuit-breaker.
Page 230
ABB | SACE Emax 2 YO-YC-YO2-YC2: Connections Further information is available on page 156, or on the site http://www.abb.com/abblibrary/ DownloadCenter/, where the wiring diagram is available 1SDM000091R0001. Diagrams 75 - 72 - 77 - 79 Information on assembly is available at the web site http://www.abb.com/abblibrary/ DownloadCenter/, in particular with the sheets kit: •...
380V…400V AC 415V…440V AC 480V…500V AC YU: Connections Further information is available on page 156, or on the site http://www.abb.com/abblibrary/ DownloadCenter/, where the wiring diagram is available 1SDM000091R0001. Diagram 73 Information on the assembly is available from the web site http://www.abb.com/abblibrary/ DownloadCenter/, in particular with the kit sheet 1SDH001000R0504.
IEC60947-2) 110V AC/DC 220V AC/DC YR: Connections Further information is available on page 156, or on the site http://www.abb.com/abblibrary/ DownloadCenter/, where the wiring diagram is available 1SDM000091R0001. Diagram 14 Information on the assembly is available from the web site http://www.abb.com/abblibrary/ DownloadCenter/, in particular with the kit sheet 1SDH001000R0606.
7 sec 380V…400V AC 440V…480V AC M: Connections Further information is available on page 156, or on the site http://www.abb.com/abblibrary/ DownloadCenter/, where the wiring diagram is available 1SDM000091R0001. S33M/1 Diagram 13 Information on the assembly is available from the web site http://www.abb.com/abblibrary/ DownloadCenter/, in particular with the kit sheet 1SDH001000R0609.
50mA @ 24V 1mA @ 5V Aux 4Q: Connections Further information is available on page 156, or on the site http://www.abb.com/abblibrary/ DownloadCenter/, where the wiring diagram is available 1SDM000091R0001. Diagram 81 Information on the assembly is available from the web site http://www.abb.com/abblibrary/ DownloadCenter/, in particular with the kit sheet 1SDH001000R0613.
Minimum load 50mA @ 24V 1mA @ 5V Aux 6Q: Connections Further information is available on page 156, or on the site http://www.abb.com/abblibrary/ DownloadCenter/, where the wiring diagram is available 1SDM000091R0001. Q/10 Diagram 1 Information on the assembly is available from the web site http://www.abb.com/abblibrary/ DownloadCenter/, in particular with the kit sheet 1SDH001000R0601.
1A cos φ 0,3 Minimum load 50mA @ 24V 1mA @ 5V Aux 15Q external: Connections Further information is available on page 156, or on the site http://www.abb.com/abblibrary/ DownloadCenter/, where the wiring diagram is available 1SDM000091R0001. Q/11 Q/12 Q/13 Q/14...
2A cos φ 0,7 1A cos φ 0,3 Minimum load 50mA @ 24V 1mA @ 5V AUP: Connections Further information is available on page 156, or on the site http://www.abb.com/abblibrary/ DownloadCenter/, where the wiring diagram is available 1SDM000091R0001. S75I/1 S75I/2 S75I/3 S75I/4...
50mA @ 24V 1mA @ 5V RTC: Connections Further information is available on page 156, or on the site http://www.abb.com/abblibrary/ DownloadCenter/, where the wiring diagram is available 1SDM000091R0001. Diagram 71 Information on the assembly is available from the web site http://www.abb.com/abblibrary/ DownloadCenter/, in particular with the kit sheet 1SDH001000R0604.
100mA @ 24V 1mA @ 5V S51: Connections Further information is available on page 156, or on the site http://www.abb.com/abblibrary/ DownloadCenter/, where the wiring diagram is available 1SDM000091R0001. Diagram 11 Information on the assembly is available from the web site http://www.abb.com/abblibrary/ DownloadCenter/, in particular with the kit sheet 1SDH001000R0605.
Minimum load 50mA @ 24V 1mA @ 5V S33/M2: Connections Further information is available on page 156, or on the site http://www.abb.com/abblibrary/ DownloadCenter/, where the wiring diagram is available 1SDM000091R0001. S33M/2 Diagram 12 Information on the assembly is available from the web site http://www.abb.com/abblibrary/ DownloadCenter/, in particular with the kit sheet 1SDH001000R0609.
• padlockable protection that inhibits the use of one or both push-buttons with the aid of a padlock. Information on the assembly is available from the web site http://www.abb.com/abblibrary/ DownloadCenter/, in particular with the kit sheet 1SDH001000R0715. IP54 protection The IP54 protection completely protects the front of the circuit-breaker, to achieve Protection class IP54.
• lock for a padlock with a diameter of 7 mm. or for a latch chain NOTE: The padlocks are at the expense of the customer. Information on the assembly is available from the web site http://www.abb.com/abblibrary/ DownloadCenter/, in particular with the kit sheet 1SDH001000R0706.
NOTE: The PLP lock can also be supplied in the presence of a "KLP lock in disconnected position". Information on the assembly is available from the web site http://www.abb.com/abblibrary/ DownloadCenter/, in particular with the kit sheet 1SDH001000R0707. KLP: key lock for connected/...
SLE: external shutter lock The SLE lock locks the shutters from the outside of the fixed part with the aid of a 4mm, 6mm or 8mm padlock. NOTE: The padlocks are at the expense of the customer. Information on the assembly is available from the web site http://www.abb.com/abblibrary/ DownloadCenter/, in particular with the kit sheet 1SDH001000R0724. DLC: Door opening lock with...
It allows you never to have two circuit-breakers in the closed position at the same time. Information on the assembly is available from the web site http://www.abb.com/abblibrary/ DownloadCenter/, in particular with the kit sheet 1SDH001000R0720. Mechanical interlock of type B -...
NOTE: Before consulting the table, check the error messages on the display. If the suggestions indicated fail to resolve the problem, contact the ABB Assistance Service supplying, if possible supplying the report produced by the Ekip Connect software.
Installation warning Voltage Module Error Error reading the module parameters. Contact ABB Further information is available from the web site http://www.abb.com/abblibrary/DownloadCenter/, whe- re the procedure is available 1SDH001000R0509. Putting into service and maintenance | 2 - Identification of alarms or failures...
> 1,5 mm ->OK Figure 107 - Checking the breaking gaps 8. Close the circuit-breaker and check dimension A. Contact ABB Sace (*) if dimension A is incorrect. If dimension A is correct, open the circuit-breaker again and re-assemble the arc chutes.