Generator and Interconnection Protection 1MRS758279 B REG615 Product version: 5.0 FP1 REG615 INTERCONNECTION PROTECTION RELAY STANDARD CONFIGURATION PROTECTION LOCAL HMI ALSO AVAILABLE 2× 3× - Disturbance and fault recorders Master Trip Master Trip - Event log and recorded data Lockout relay Lockout relay Configuration...
Page 5
Generator and Interconnection Protection 1MRS758279 B REG615 Product version: 5.0 FP1 REG615 GENERATOR PROTECTION RELAY STANDARD CONFIGURATION PROTECTION LOCAL HMI ALSO AVAILABLE 2× 3× - Disturbance and fault recorders Master Trip Master Trip - Event log and recorded data Lockout relay Lockout relay Configuration...
Page 6
Generator and Interconnection Protection 1MRS758279 B REG615 Product version: 5.0 FP1 REG615 GENERATOR PROTECTION RELAY STANDARD CONFIGURATION PROTECTION LOCAL HMI ALSO AVAILABLE 2× 3× - Disturbance and fault recorders Master Trip Master Trip - Event log and recorded data Lockout relay Lockout relay Configuration...
Generator and Interconnection Protection 1MRS758279 B REG615 Product version: 5.0 FP1 3. Protection functions and when to disconnect from the grid. The voltage vector shift The generator protection relay offers protection functionality for protection detects islanding from the grid by measuring...
Page 10
Generator and Interconnection Protection 1MRS758279 B REG615 Product version: 5.0 FP1 Common point of coupling distributed power generation into the utility network REG615 Std. conf. ANSI SYNC 27RT U<RT 32Q, 27 Q>→, 3U< 32R/32O P>/Q> 47O-/59 U2>/3U> 47U+/27 U1</3U< 50L/50NL FUSEF f</f>, df/dt...
Page 11
Generator and Interconnection Protection 1MRS758279 B REG615 Product version: 5.0 FP1 Common point of coupling distributed power generation into the utility network REG615 Std. conf. ANSI SYNC 27RT U<RT 32Q, 27 Q>→, 3U< 32R/32O P>/Q> 47O-/59 U2>/3U> 47U+/27 U1</3U< 50L/50NL FUSEF f</f>, df/dt...
Page 13
Figure 7 protection is implemented with two REG615 Three-phase directional overcurrent protection, three-phase generator protection relays. One REG615 takes care of the voltage protection, positive-sequence and negative-sequence generator protection with 100% stator earth-fault protection voltage protection functions must be added with the and the other REG615 provides the generator differential Application Configuration tool.
Page 14
Medium-sized generator in block connection with a transformer protection application example with standard configuration C and RET615 Figure 8 generator protection is implemented with REG615 a transformer. A single-phase voltage transformer is connected generator protection relay. Transformer protection is to the generator neutral for the residual overvoltage protection.
615 series relays without the optional power systems. To facilitate the system engineering, ABB's single-line diagram feature are used. The Web HMI of relays are supplied with connectivity packages. The...
GOOSE communication GUID-4D002AA0-E35D-4D3F-A157-01F1A3044DDB V4 EN Figure 9. ABB power system example using Relion relays, COM600S and MicroSCADA Pro/System 800xA 6. Control If the amount of available binary inputs or outputs of the chosen REG615 integrates functionality for the control of a circuit standard configuration is not sufficient, the standard breaker via the front panel HMI or by means of remote controls.
Generator and Interconnection Protection 1MRS758279 B REG615 Product version: 5.0 FP1 the relevant primary devices. Interlocking schemes required by The protection relay has the following power quality monitoring the application are configured using the signal matrix or the functions. application configuration functionality of PCM600. Depending •...
Generator and Interconnection Protection 1MRS758279 B REG615 Product version: 5.0 FP1 11. Recorded data block, or by both. The available measurement modes include The relay has the capacity to store the records of the 128 latest DFT, RMS and peak-to-peak. Fault records store relay fault events.
Generator and Interconnection Protection 1MRS758279 B REG615 Product version: 5.0 FP1 14. Self-supervision residual current input, three phase-voltage inputs and one The relay’s built-in self-supervision system continuously residual voltage input, and one voltage input that is used either monitors the state of the relay hardware and the operation of for synchro-check or for the 3rd harmonic-based stator earth- the relay software.
Generator and Interconnection Protection 1MRS758279 B REG615 Product version: 5.0 FP1 Table 4. Input/output overview Std. conf. Order code digit Analog channels Binary channels 4 PO + 6 SO AE / AF 4 PO + 2 SO + 3 HSO...
Page 21
Generator and Interconnection Protection 1MRS758279 B REG615 Product version: 5.0 FP1 615 relays with process bus based applications use IEEE 1588 communication. The network redundancy is based on two for high accuracy time synchronization. complementary protocols defined in the IEC 62439-3 standard: PRP and HSR protocols.
Page 22
Generator and Interconnection Protection 1MRS758279 B REG615 Product version: 5.0 FP1 COM600 Devices not supporting HSR SCADA Ethernet switch Redundancy Redundancy Redundancy IEC 61850 HSR REF620 RET620 REM620 REF615 REF615 GUID-7996332D-7FC8-49F3-A4FE-FB4ABB730405 V1 EN Figure 12. High availability seamless redundancy (HSR) solution The choice between the HSR and PRP redundancy protocols switch-over.
Page 23
Generator and Interconnection Protection 1MRS758279 B REG615 Product version: 5.0 FP1 Client A Client B Network A Network B Managed Ethernet switch Managed Ethernet switch with RSTP support with RSTP support GUID-AB81C355-EF5D-4658-8AE0-01DC076E519C V4 EN Figure 13. Self-healing Ethernet ring solution All communication connectors, except for the front port records are supported.
Page 24
Generator and Interconnection Protection 1MRS758279 B REG615 Product version: 5.0 FP1 The relay supports the following high accuracy time • Layer 2 mapping synchronization method with a time-stamping resolution of 4 µs • Peer to peer delay calculation required especially in process bus applications.
Generator and Interconnection Protection 1MRS758279 B REG615 Product version: 5.0 FP1 19. Technical data Table 6. Dimensions Description Value Width Frame 177 mm Case 164 mm Height Frame 177 mm (4U) Case 160 mm Depth 201 mm (153 + 48 mm)
Page 26
Generator and Interconnection Protection 1MRS758279 B REG615 Product version: 5.0 FP1 Table 9. Binary inputs Description Value Operating range ±20% of the rated voltage Rated voltage 24...250 V DC Current drain 1.6...1.9 mA Power consumption 31.0...570.0 mW Threshold voltage 16...176 V DC Reaction time <3 ms...
Page 27
Generator and Interconnection Protection 1MRS758279 B REG615 Product version: 5.0 FP1 Table 12. Signal outputs and IRF output Description Value Rated voltage 250 V AC/DC Continuous contact carry Make and carry for 3.0 s 10 A Make and carry 0.5 s 15 A Breaking capacity when the control-circuit time constant L/R<40 ms, at...
Page 28
Generator and Interconnection Protection 1MRS758279 B REG615 Product version: 5.0 FP1 Table 15. High-speed output HSO with BIO0007 Description Value Rated voltage 250 V AC/DC Continuous contact carry Make and carry for 3.0 s 15 A Make and carry for 0.5 s 30 A Breaking capacity when the control-circuit time constant L/R <40 ms, at...
Page 29
Generator and Interconnection Protection 1MRS758279 B REG615 Product version: 5.0 FP1 Table 20. Electromagnetic compatibility tests Description Type test value Reference 1 MHz/100 kHz burst disturbance test IEC 61000-4-18 IEC 60255-26, class III IEEE C37.90.1-2002 • Common mode 2.5 kV •...
Page 30
Generator and Interconnection Protection 1MRS758279 B REG615 Product version: 5.0 FP1 Table 20. Electromagnetic compatibility tests, continued Description Type test value Reference Power frequency immunity test Binary inputs only IEC 61000-4-16 IEC 60255-26, class A • Common mode 300 V rms •...
Page 31
Generator and Interconnection Protection 1MRS758279 B REG615 Product version: 5.0 FP1 Table 23. Environmental tests Description Type test value Reference Dry heat test • 96 h at +55ºC IEC 60068-2-2 Dry cold test • 96 h at -25ºC IEC 60068-2-1 •...
Page 32
Generator and Interconnection Protection 1MRS758279 B REG615 Product version: 5.0 FP1 Protection functions Table 27. Three-phase non-directional overcurrent protection (PHxPTOC) Characteristic Value Operation accuracy Depending on the frequency of the measured current: f ±2 Hz PHLPTOC ±1.5% of the set value or ±0.002 × I PHHPTOC ±1.5% of set value or ±0.002 ×...
Page 33
Generator and Interconnection Protection 1MRS758279 B REG615 Product version: 5.0 FP1 Table 29. Three-phase directional overcurrent protection (DPHxPDOC) Characteristic Value Operation accuracy Depending on the frequency of the current/voltage measured: f ±2 Hz DPHLPDOC Current: ±1.5% of the set value or ±0.002 × I Voltage: ±1.5% of the set value or ±0.002 ×...
Page 34
Generator and Interconnection Protection 1MRS758279 B REG615 Product version: 5.0 FP1 Table 31. Three-phase voltage-dependent overcurrent protection (PHPVOC) Characteristic Value Operation accuracy Depending on the frequency of the measured current and voltage: ±2 Hz Current: ±1.5% of the set value or ± 0.002 × I Voltage: ±1.5% of the set value or ±0.002 ×...
Page 35
Generator and Interconnection Protection 1MRS758279 B REG615 Product version: 5.0 FP1 Table 33. Non-directional earth-fault protection (EFxPTOC) Characteristic Value Operation accuracy Depending on the frequency of the measured current: f ±2 Hz EFLPTOC ±1.5% of the set value or ±0.002 × I EFHPTOC ±1.5% of set value or ±0.002 ×...
Page 36
Generator and Interconnection Protection 1MRS758279 B REG615 Product version: 5.0 FP1 Table 35. Directional earth-fault protection (DEFxPDEF) Characteristic Value Operation accuracy Depending on the frequency of the measured current: f ±2 Hz DEFLPDEF Current: ±1.5% of the set value or ±0.002 × I Voltage ±1.5% of the set value or ±0.002 ×...
Page 37
Generator and Interconnection Protection 1MRS758279 B REG615 Product version: 5.0 FP1 Table 36. Directional earth-fault protection (DEFxPDEF) main settings Parameter Function Value (Range) Step Start value DEFLPDEF 0.010...5.000 × I 0.005 DEFHPDEF 0.10...40.00 × I 0.01 Directional mode DEFLPDEF and DEFHPDEF...
Page 38
Generator and Interconnection Protection 1MRS758279 B REG615 Product version: 5.0 FP1 Table 39. Negative-sequence overcurrent protection (NSPTOC) Characteristic Value Operation accuracy Depending on the frequency of the measured current: f ±1.5% of the set value or ±0.002 × I Minimum...
Page 39
Generator and Interconnection Protection 1MRS758279 B REG615 Product version: 5.0 FP1 Table 42. Negative-sequence overcurrent protection for machines (MNSPTOC) main settings Parameter Function Value (Range) Step 0.01...0.50 × I Start value MNSPTOC 0.01 Operating curve type MNSPTOC Definite or inverse time...
Page 40
Generator and Interconnection Protection 1MRS758279 B REG615 Product version: 5.0 FP1 Table 45. Three-phase undervoltage protection (PHPTUV) Characteristic Value Operation accuracy Depending on the frequency of the voltage measured: f ±2 Hz ±1.5% of the set value or ±0.002 × U...
Page 41
Generator and Interconnection Protection 1MRS758279 B REG615 Product version: 5.0 FP1 Table 48. Three-phase overvoltage protection (PHPTOV) main settings Parameter Function Value (Range) Step Start value PHPTOV 0.05...1.60 × U 0.01 Time multiplier PHPTOV 0.05...15.00 0.01 Operate delay time PHPTOV 40...300000 ms...
Page 42
Generator and Interconnection Protection 1MRS758279 B REG615 Product version: 5.0 FP1 Table 51. Negative-sequence overvoltage protection (NSPTOV) Characteristic Value Operation accuracy Depending on the frequency of the voltage measured: f ±1.5% of the set value or ±0.002 × U Minimum...
Page 43
Generator and Interconnection Protection 1MRS758279 B REG615 Product version: 5.0 FP1 Table 54. Frequency protection (FRPFRQ) main settings Parameter Function Value (Range) Step Operation mode FRPFRQ 1 = Freq< 2 = Freq> 3 = df/dt 4 = Freq< + df/dt 5 = Freq>...
Page 44
Generator and Interconnection Protection 1MRS758279 B REG615 Product version: 5.0 FP1 Table 57. Three-phase thermal protection for feeders, cables and distribution transformers (T1PTTR) Characteristic Value Operation accuracy Depending on the frequency of the measured current: f ±2 Hz Current measurement: ±1.5% of the set value or ±0.002 × I (at currents in the range of 0.01...4.00 ×...
Page 45
Generator and Interconnection Protection 1MRS758279 B REG615 Product version: 5.0 FP1 Table 61. Circuit breaker failure protection (CCBRBRF) Characteristic Value Operation accuracy Depending on the frequency of the measured current: f ±2 Hz ±1.5% of the set value or ±0.002 × I Operate time accuracy ±1.0% of the set value or ±20 ms...
Page 46
Generator and Interconnection Protection 1MRS758279 B REG615 Product version: 5.0 FP1 Table 65. Arc protection (ARCSARC) Characteristic Value Operation accuracy ±3% of the set value or ±0.01 × I Operate time Minimum Typical Maximum Operation mode = "Light 9 ms...
Page 47
Generator and Interconnection Protection 1MRS758279 B REG615 Product version: 5.0 FP1 Table 69. Stabilized and instantaneous differential protection for machines (MPDIF) Characteristic Value Operation accuracy Depending on the frequency of the current measured: f ±2 Hz ±3% of the set value or ±0.002 x I...
Page 48
Generator and Interconnection Protection 1MRS758279 B REG615 Product version: 5.0 FP1 Table 72. Third harmonic-based stator earth-fault protection (H3EFPSEF) main settings Parameter Function Value (Range) Step Beta H3EFPSEF 0.50...10.00 0.01 Voltage N 3.H Lim H3EFPSEF 0.005...0.200 × U 0.001 Operate delay time H3EFPSEF 20...300000 ms...
Page 49
Generator and Interconnection Protection 1MRS758279 B REG615 Product version: 5.0 FP1 Table 75. Reverse power/directional overpower protection (DOPPDPR) Characteristic Value Depending on the frequency of the measured current and voltage: Operation accuracy f = f ±2 Hz Power measurement accuracy ±3% of the set value or ±0.002 × S Phase angle: ±2°...
Page 50
Generator and Interconnection Protection 1MRS758279 B REG615 Product version: 5.0 FP1 Table 78. Three-phase underexcitation protection (UEXPDIS) main settings Parameter Function Value (Range) Step Diameter UEXPDIS 1...6000 %Z Offset UEXPDIS -1000...1000 %Z Displacement UEXPDIS -1000...1000 %Z Operate delay time UEXPDIS 60...200000 ms...
Page 51
Generator and Interconnection Protection 1MRS758279 B REG615 Product version: 5.0 FP1 Table 82. Out-of-step protection (OOSRPSB) main settings Parameter Function Value (Range) Step Oos trip mode OOSRPSB 1 = Way in 2 = Way out 3 = Adaptive Forward reach OOSRPSB 0.00...6000.00 Ω...
Page 52
Generator and Interconnection Protection 1MRS758279 B REG615 Product version: 5.0 FP1 Interconnection functions Table 84. Directional reactive power undervoltage protection (DQPTUV ) Characteristic Value Operation accuracy Depending on the frequency of the measured current and voltage: ±2 Hz Reactive power range |PF| <0.71 Power: ±3.0% or ±0.002 ×...
Page 53
Generator and Interconnection Protection 1MRS758279 B REG615 Product version: 5.0 FP1 Table 87. Low-voltage ride-through protection (LVRTPTUV) main settings Parameter Function Value (Range) Step Voltage start value LVRTPTUV 0.05...1.20 × U 0.01 Num of start phases LVRTPTUV 4 = Exactly 1 of 3...
Page 54
Generator and Interconnection Protection 1MRS758279 B REG615 Product version: 5.0 FP1 Table 89. Voltage vector shift protection (VVSPPAM) main settings Parameter Function Value (Range) Step Start value VVSPPAM 2.0...30.0° Over Volt Blk value VVSPPAM 0.40...1.50 × Un 0.01 Under Volt Blk value VVSPPAM 0.15...1.00 ×...
Page 55
Generator and Interconnection Protection 1MRS758279 B REG615 Product version: 5.0 FP1 Power quality functions Table 90. Voltage variation (PHQVVR) Characteristic Value Operation accuracy ±1.5% of the set value or ±0.2% of reference voltage Reset ratio Typically 0.96 (Swell), 1.04 (Dip, Interruption) Table 91.
Page 56
Generator and Interconnection Protection 1MRS758279 B REG615 Product version: 5.0 FP1 Control functions Table 92. Synchronism and energizing check (SECRSYN) Characteristic Value Operation accuracy Depending on the frequency of the voltage measured: f ±1 Hz Voltage: ±3.0% of the set value or ±0.01 × U Frequency: ±10 mHz...
Page 57
Generator and Interconnection Protection 1MRS758279 B REG615 Product version: 5.0 FP1 Supervision functions Table 94. Circuit-breaker condition monitoring (SSCBR) Characteristic Value Current measuring accuracy ±1.5% or ±0.002 × I (at currents in the range of 0.1…10 × I ±5.0% (at currents in the range of 10…40 × I Operate time accuracy ±1.0% of the set value or ±20 ms...
Page 58
Generator and Interconnection Protection 1MRS758279 B REG615 Product version: 5.0 FP1 Measurement functions Table 99. Three-phase current measurement (CMMXU) Characteristic Value Operation accuracy Depending on the frequency of the measured current: f ±2 Hz ±0.5% or ±0.002 × I (at currents in the range of 0.01...4.00 × I Suppression of harmonics DFT: -50 dB at f = n ×...
Page 59
Generator and Interconnection Protection 1MRS758279 B REG615 Product version: 5.0 FP1 Table 104. Sequence voltage measurement (VSMSQI) Characteristic Value Operation accuracy Depending on the frequency of the voltage measured: f ±2 Hz At voltages in range 0.01…1.15 × U ±1.0% or ±0.002 × U Suppression of harmonics DFT: -50 dB at f = n ×...
Page 60
Generator and Interconnection Protection 1MRS758279 B REG615 Product version: 5.0 FP1 Other functions Table 108. Pulse timer (PTGAPC) Characteristic Value Operate time accuracy ±1.0% of the set value or ±20 ms Table 109. Time delay off (8 pcs) (TOFPAGC) Characteristic...
Generator and Interconnection Protection 1MRS758279 B REG615 Product version: 5.0 FP1 20. Local HMI default single line diagram. The SLD view can also be accessed The relay is available with two optional displays, a large one and using the Web browser-based user interface. The default SLD a small one.
(PST), a Next-Generation Order Number circuiting the CT secondary circuits when a relay unit is Tool, supports order code creation for ABB Distribution withdrawn from its case. The relay case is further provided with Automation IEC products with emphasis on but not exclusively a mechanical coding system preventing the current measuring for the Relion product family.
Generator and Interconnection Protection 1MRS758279 B REG615 Product version: 5.0 FP1 24. Accessories and ordering data Table 113. Cables Item Order number Optical sensor for arc protection, cable length 1.5 m 1MRS120534-1.5 Optical sensor for arc protection, cable length 3.0 m 1MRS120534-3 Optical sensor for arc protection, cable length 5.0 m...
Web browser Table 115. Tools Description Version PCM600 2.6 (Rollup 20150626) or later Web browser IE 8.0, IE 9.0, IE 10.0 or IE 11.0 REG615 Connectivity Package 5.1 or later...
Generator and Interconnection Protection 1MRS758279 B REG615 Product version: 5.0 FP1 27. Terminal diagrams GUID-4BA6AD56-1833-4BA6-B3CC-3C44FD9767BF V1 EN Figure 19. Terminal diagram of standard configuration A...
Page 67
Generator and Interconnection Protection 1MRS758279 B REG615 Product version: 5.0 FP1 GUID-7E974B34-D8B8-4114-A24A-40F38BECF594 V1 EN Figure 20. Terminal diagram of standard configuration C...
Page 68
Generator and Interconnection Protection 1MRS758279 B REG615 Product version: 5.0 FP1 GUID-6756612D-B6DA-4B52-822D-B2794FADCC23 V1 EN Figure 21. Terminal diagram of standard configuration D...
Relion 615 series. Certificate number: 7410570I-OPE/INC products and services. 15-1136. The latest relevant information on the REG615 protection and DNV GL has issued an IEC 61850 Edition 1 Certificate Level A1 control relay is found on the product page. Scroll down the ®...
Generator and Interconnection Protection 1MRS758279 B REG615 Product version: 5.0 FP1 30. Functions, codes and symbols Table 117. Functions included in the relay Function IEC 61850 IEC 60617 IEC-ANSI Protection Three-phase non-directional overcurrent protection, PHLPTOC1 3I> (1) 51P-1 (1) low stage...
Page 71
Generator and Interconnection Protection 1MRS758279 B REG615 Product version: 5.0 FP1 Table 117. Functions included in the relay, continued Function IEC 61850 IEC 60617 IEC-ANSI Overexcitation protection OEPVPH1 U/f> (1) 24 (1) Three-phase thermal protection for feeders, cables T1PTTR1 3Ith>F (1)
Page 72
Generator and Interconnection Protection 1MRS758279 B REG615 Product version: 5.0 FP1 Table 117. Functions included in the relay, continued Function IEC 61850 IEC 60617 IEC-ANSI Reverse power/directional overpower protection DOPPDPR1 P>/Q> (1) 32R/32O (1) DOPPDPR2 P>/Q> (2) 32R/32O (2) DOPPDPR3 P>/Q>...
Page 73
Generator and Interconnection Protection 1MRS758279 B REG615 Product version: 5.0 FP1 Table 117. Functions included in the relay, continued Function IEC 61850 IEC 60617 IEC-ANSI Fault record FLTRFRC1 FAULTREC (1) FAULTREC (1) Three-phase current measurement CMMXU1 3I (1) 3I (1)
Generator and Interconnection Protection 1MRS758279 B REG615 Product version: 5.0 FP1 Table 117. Functions included in the relay, continued Function IEC 61850 IEC 60617 IEC-ANSI Move (8 pcs) MVGAPC1 MV (1) MV (1) MVGAPC2 MV (2) MV (2) Generic control point (16 pcs)
Page 76
Contact us ABB Distribution Solutions Distribution Automation P.O. Box 699 FI-65101 VAASA, Finland Phone +358 10 22 11 www.abb.com/mediumvoltage www.abb.com/substationautomation ABB Distribution Automation Maneja Works Vadodara-390013, India Phone +91 265 2604386 +91 265 2638922 www.abb.com/mediumvoltage www.abb.com/substationautomation...