About this document ..................5 Safety ......................9 Safety instructions ................... 9 Safety regulations for the method of operation ..........11 Standards and directives complied with ............13 Release Notes ....................14 Structure and function ................15 Overview ....................... 15 3.1.1 Details for ordering .................
Page 4
Planning ....................... 47 Compatibility ....................47 Defining the mounting site and configuration of the lines ......48 Planning the detector line ................48 Planning the control line ................49 Planning contact input ................... 49 Environmental influences ................49 Filling out the configuration sheet ..............50 Mounting / Installation ................
FDCIO223. Following the instructions consistently will ensure that the product can be used safely and without any problems. This document is only valid for input/output modules FDCIO223 with a product version (ES) ≤45. All input/output modules FDCIO223 with a product version (ES) ≥50 are described in document 09122 from modification index 'f'.
Page 6
About this document Document identification Position Information Title page Product type Product designation Document type Last page, bottom left Document ID ID_ModificationIndex_Language_COUNTRY Edition date Last page, bottom right Manual Register Conventions for text marking Markups Special markups are shown in this document as follows: ⊳...
Page 7
Maintenance and Commissioning Link; interface to the detector exchanger and tester Polycarbonate (plastic) Reference documents Document ID Title 009124 Mounting of Input/output module FDCIO223, Mounting of housing FDCH221 001204 Fire alarm signal in areas at risk of explosion 008331 List of compatibility (for 'Sinteso' product line) A6V10229261...
Page 8
About this document Revision history Document ID Edition date Brief description 009122_e1_en_-- 2015-10-06 Revisions for ES ≤45 included. 009122_e_en_-- 2009-11 Housing FDCH29x replaced with FDCH221 Editorial adjustments made. 009122_d_en_-- 2009-07 Editorial changes made. New 'Index' chapter. 009122_c_en_-- 2007-09 Descriptions of 'Control with confirmation' removed.
Safety Safety Safety instructions The safety notices must be observed in order to protect people and property. The safety notices in this document contain the following elements: Symbol for danger Signal word Nature and origin of the danger ...
Page 10
Safety Signal word The signal word classifies the danger as defined in the following table: Signal word Danger level DANGER DANGER identifies a dangerous situation, which will result directly in death or serious injury if you do not avoid this situation.
Safety regulations for the method of operation National standards, regulations and legislation Siemens products are developed and produced in compliance with the relevant European and international safety standards. Should additional national or local safety standards or legislation concerning the planning, mounting, installation,...
Page 12
Modules and spare parts Components and spare parts must comply with the technical specifications defined by Siemens. Only use products specified or recommended by Siemens. Only use fuses with the specified fuse characteristics and which have been adapted to the connected load.
We are grateful for any suggestions for improvement. Standards and directives complied with A list of the standards and directives complied with is available from your Siemens contact. Building Technologies 009122_e1_en_--...
Safety Release Notes Limitations to the configuration or use of devices in a fire detection installation with a particular firmware version are possible. WARNING Limited or non-existent fire detection Personal injury and damage to property in the event of a fire. Read the 'Release Notes' before you plan and/or configure a fire detection ...
With the safety barrier, it is also possible to connect intrinsically safe detectors (ex-zones 1 and 2) If the input/output module FDCIO223 is operated in conjunction with a fire detection system FS20/FS720, only collective detector lines and monitored equipment control are supported. It is not possible for contacts to be connected.
Structure and function 3.1.1 Details for ordering Type Order no. Designation FDCIO223 S24218-B102-A1 Input / output module (transponder) See also Enclosed accessories [ 44] Setup The modules consist of the module carrier, the printed circuit board and the cover cap.
Structure and function 3.2.2 Circuit board view Circuit board view 1 Ground connection 2 Shielding connection for inputs/outputs 'I/O 1' and 'I/O 2' 3 Connection for input/output 'I/O 2' 4 Connection for input/output 'I/O 1' 5 Jumper for polarization of monitoring for input/output 'I/O 2' 6 Jumper for polarization of monitoring for input/output 'I/O 1' 7 Push button for calibrating control lines 8 Jumper for ground fault monitoring of inputs/outputs 'I/O 1' and 'I/O 2'...
Structure and function 3.2.3 Indication elements 3.2.3.1 Input/output module status display Primary side LEDs Green Yellow Meaning 'PWR PRIM' 'FAULT PRIM' (Ref 12) (Ref 12) Flashes every 4 s Normal condition Flashes every 4 s Flashes every 4 s Test mode Flashes every 4 s Flashes once a Localization mode...
Structure and function 3.2.3.2 Status display for the lines There are both red and green LEDs for each input/output and these are used to indicate the status (LED 'I/O 1' and 'I/O 2'). Their meaning depends on how the input/output is configured. Input/output is configured as an input (detector line or contact input) Green...
Structure and function 3.2.4 Adjustment elements Supervision I/O 1 I/O 2 Adjustment elements Legend Jumper Function Position Meaning Ground fault monitoring Activated (Ref 8) Deactivated Supervision Input/output 1: norm Setting for: I/O 1 Polarity during monitoring Control line featuring identical-polarity monitoring ...
3.3.1 Overview A distinction is made in terms of the function between the primary and secondary sides of the FDCIO223 input/output module. The primary side represents the connection to the FDnet/C-NET. Both inputs/outputs are triggered on the secondary side. The inputs/outputs can be used as follows: GMT Siemens/Cerberus collective detector lines ...
Structure and function 3.3.2 Input/output module primary side Communication Communication with the control panel takes place via the FDnet/C-NET detector line. Configuration is performed on the control panel. Line separator All FDnet/C-NET devices are equipped with a line separator. The FDnet/C-NET device is equipped with electronic switches which isolate the defective part in case of a short-circuit on the detector line.
Use 'slow-blow' fuses. Do not connect the 24 V supply until you have configured the input/output module. FDCIO223 DC 24 V DC 24 V R = 30...3,3 k Fuses 1 DC 24 V supply fuse 2 Control line fuse...
Page 24
Structure and function Connecting the 24 V supply Connecting the 24 V supply 1 Wires 2 Pluggable terminal blocks 3 Connection for the 24 V secondary side supply WARNING Incorrectly connected 24 V supply Damage to the device due to current flowing in the wrong direction Observe the polarity of the power supply source when making the ...
Instead, activation in test mode/inspection mode will merely be signaled by means of LEDs on the input/output module. If the input/output module FDCIO223 is operated with a control panel FS20/FS720, no control outputs will be triggered in the event of activation in test mode/inspection mode.
Structure and function 3.3.5 Ground fault monitoring The secondary side is monitored for ground faults regardless of mode. Ground fault monitoring can be deactivated with a jumper. The setting for ground fault monitoring always applies to both inputs/outputs. If intrinsically safe detectors are connected, ground fault monitoring must be deactivated.
1 and input/output 2. Configuration Input/output 1 Input/output 2 Siemens/Cerberus detector line SynoLINE300 detector line Contact input Control line (monitored/non-monitored) Comment The device is configured on the control panel with the aid of the configuration tool.
‒ Third-party products in accordance with 'Industrial conventional' (Synova300C) It is not possible to operate Siemens/Cerberus detectors and SynoLINE300 detectors simultaneously on the same detector line. The compatible detector types are listed in the 'Collective compatibility' chapter and in the 'List of compatibility'.
Structure and function 3.4.1.2 Detector line design Permissible cable types The detector line is compatible with the following cables: Shielded cables Unshielded cables The table below shows the permissible cable values: Cable values Detector line without safety Detector line with safety barrier barrier Inductance...
Page 30
Structure and function Monitoring of detector lines The input/output module monitors the line resistance of the detector line during operation. The line resistance is adjusted precisely in each of the following cases: On initial start-up When an alarm has been reset ...
3.4.1.3 Connection of intrinsically safe detectors in ex-zone 1 Safety barrier SB3 can also be connected to the FDCIO223 input/output module. This allows intrinsically safe detectors to be operated in ex-zone 1+2. If you operate the module in conjunction with an SB3 safety barrier, the following points must be observed in particular: The line resistance must not exceed 50 Ω...
Structure and function 3.4.1.4 Alarm verification To help prevent false alarms, the FDCIO223 input/output module features a form of alarm verification that can be activated as required. When alarm verification is activated, any alarm (1) that occurs will first be stored by the input/output module.
Structure and function 3.4.1.5 Monitoring The input/output module monitors the detector line for the following criteria: Alarm Open line (creeping) Short circuit (creeping) Ground fault (joint) 3.4.2 Configuration as a contact input The inputs/outputs of the input/output module can be configured as contact inputs. The following configurations are possible: Status inputs Status inputs trigger a status change as soon as they are activated.
Page 34
Structure and function Circuit The figure below shows the various circuit options available for contact inputs. Circuit for contact inputs 1 DC 24 V supply fuse 2…3 Monitoring for open line and short circuit 5 Monitoring for open line only The contact inputs must be potential-free.
If a short circuit occurs on the control line, the 24 V supply voltage must be disconnected. The FDCIO223 input/output module does not contain any fuses. Therefore, contact protection measures must be implemented by the customer. Within the context of control, the secondary side supply voltage (24 V DC) is applied to the relevant output via a relay.
Page 36
Structure and function Monitoring You have the option of monitoring the control line. Monitored control lines are monitored for the following criteria: Open line (creeping) Short circuit (creeping) Ground fault (only both inputs/outputs jointly, no line-specific fault message) ...
Page 37
Structure and function Circuit featuring identical-polarity monitoring FDCIO223 24 V R = 30...3,3 k Circuit for control lines with identical-polarity monitoring 1 External fuse (to be provided by customer) Circuit featuring reverse-polarity monitoring FDCIO223 24 V 3.3 k 10 V...
Page 38
Structure and function Calibration of load resistances To ensure that any load resistances (particularly those associated with coils) can be monitored without any problems, the connected line must be calibrated during commissioning. During calibration, the load resistance and the line resistance are measured and stored as reference values.
Structure and function 3.4.3.2 Control without confirmation Configuration The following configurations are supported in the case of control without confirmation: Once activated, the control remains permanently active Once activated, the control only remains active for a certain time. How long the ...
Structure and function Behavior in the event of an error (control panel-specific) Error Configuration option Failure of 24 V power supply Open (configuration not possible) Error involving control panel (e.g., Relay remains unchanged communication with control panel Relay deactivated ...
Structure and function Diagnosis levels The FDCIO223 input/output module monitors its operation largely autonomously. The following diagnosis levels are derived from the different control measurements: Normal Observe information Replacement recommended Replacement necessary Fault For details, see table below.
Page 42
Structure and function Status queries with detector exchanger and tester FDUD292 or intelligent detector tester FDUD293 are only possible with devices of the 'Sinteso' product line on the FDnet. Building Technologies 009122_e1_en_-- Fire Safety 2015-10-06...
Structure and function Behavior in degraded mode The following applies for FDnet/C-NET: When the main processor of the fire control panel fails, the control panel is in degraded mode operation. Depending on the control panel type, the fire control panel can continue to perform the most important alarming and signaling functions in degraded mode operation.
Structure and function Accessories 3.7.1 Enclosed accessories The FDCIO223 input/output module is supplied with the following accessories: 2x resistors 560 Ω, 0.25 W 2x resistors 680 Ω, 0.25 W 2x resistors 2.7 kΩ, 0.25 W 2x resistors 3.3 kΩ, 0.25 W ...
Structure and function 3.7.2.3 Housing FDCH221 To protect against dust and wetness Compatible with: Multi line separator module FDCL221-M – Input module FDCI22x(-CN) – Input/output module FDCIO22x(-CN) – Order no.: S54312-F3-A1 3.7.2.4 Connection terminal DBZ1190AB For connecting cables ...
Structure and function 3.7.2.7 Cable ties 2.4 x 137 For strain relief on the connection wires or generally for attachment Made from polyamide Compatible with: Input module FDCI22x(-CN) – Input/output module FDCIO22x(-CN) – FDCL221 line separator – Multi line separator module FDCL221M –...
3. Define the values and characteristics of the fuses as well as their mounting site ‒ 24 V supply (primary side) ‒ Outputs (secondary side) Compatibility The input/output module FDCIO223 is compatible with the AlgoRex, SIGMASYS, and FS2-/FS720 fire detection systems. For details, see 'List of compatibility'. Building Technologies 0009122_e1_en_--...
Mounting site ________________ Mode of mounting □ Without housing □ With housing FDCH221 Configuration of input/output □ Siemens/Cerberus detector line, SynoLINE600 'I/O 1' □ SynoLINE300 detector line □ Contact input □ Control line without confirmation □ Inverted control □ Reverse-polarity monitoring of control Configuration of input/output □...
Planning Planning the control line Define the values of the individual parameters for the relevant inputs/outputs (see table). Parameters Input/output 'I/O 1' Input/output 'I/O 2' Polarity of control and □ Same polarity □ Same polarity monitoring systems in □ Reverse polarity □...
Planning Filling out the configuration sheet 1. Copy out the configuration sheet. You will find it in the appendix. 2. Fill out the configuration sheet. 3. Hand over copies of the completed configuration sheet to the installer and the service technician. See also ...
Mounting / Installation Mounting / Installation The procedure followed during mounting depends on whether the input/output module FDCIO223 is installed with or without a housing. WARNING Electrical voltage on output cables! Mortal danger due to electric shock! Ensure that the cables are not supplied with voltage during installation.
Page 52
Mounting / Installation Cable with diameter > 1.5 mm² If the cable diameters on the inputs/outputs are greater than 1.5 mm , auxiliary terminals must be used: In the case of cables with a diameter of 1.5…2.5 mm , connection terminal ...
Mounting / Installation Installation without housing Note the positive and negative poles. Only connect one wire per terminal. This is the only way to ensure the connection is failure-free for the entire service life of the device. If you are installing the module without the housing, proceed as follows: 1.
Mounting / Installation Connecting input/output module Circuit board view Connect the module in accordance with the corresponding connection diagrams. Note the positive and negative poles. Only connect one wire per terminal. This is the only way to ensure the connection is failure-free for the entire service life of the device.
Page 55
Mounting / Installation The shielding of the FDnet/C-NET detector line must never be used as a secondary-side ground potential or connected to other shields. If shields are connected, this can result in faults on the FDnet/C-NET detector line. Terminals 15 and 16 are used exclusively for looping through the shields. See also ...
Commissioning Commissioning The device is commissioned via the control panel. The exact procedure is described in the control panel documentation. Conduct a performance check once commissioning is complete. If the input/output module is to be used for control purposes, the control lines will need to be calibrated during commissioning.
Maintenance / Repair Maintenance / Repair Status query The FDCIO223 input/output module is equipped with the MC link (Maintenance and Commissioning Link). Using this interface, it is possible to read out data from the device the detector exchanger and tester FDUD292 or the intelligent detector tester FDUD293.
Can be configured as: Siemens/Cerberus type SynoLINE300 type Number of detectors per detector Max. 32 line Collective detector connection factor with Siemens/Cerberus type Current consumption of all detectors Max. 3.2 mA on a SynoLINE300 line Building Technologies 009122_e1_en_-- Fire Safety 2015-10-06...
Page 59
Specifications Operating voltage / quiescent current: Siemens/Cerberus type 20 V / max. 4.5 mA SynoLINE300 type 20 V / max. 17 mA Line resistance / line capacitance: Without safety barrier SB3 ≤150 Ω / ≤1 μF With safety barrier SB3 ≤...
Page 60
Specifications Contact input Measurement voltage Approx. 2 V Measurement current Max. 32 mA Effective terminating resistances 3.3 kΩ; +/-1 %; 0.25 W 560 Ω; +/-1 %; 0.25 W Line resistance Max. 150 Ω Line capacitance Max. 1 µF Monitored for: Short circuit (if configured) ...
Page 61
Specifications Connections FDnet/C-NET detector line, inputs and outputs, shielding, external DC 24 V: Design Screw terminals on plug Cable cross section 0.2…1.5 mm MC link Plug connection Ambient conditions Operating temperature/permissible -25…+60 °C ambient temperature Storage temperature -30…+65 °C Air humidity ≤95 % rel.
Specifications Dimensions Dimensions Environmental compatibility Reusable materials Electronic parts and synthetic materials can be easily separated Halogen-free synthetic materials, marked by embossed code The synthetic materials used do not generate any toxic substances during combustion Larger synthetic parts are marked in accordance with ISO 11469. The material codes for basic polymers conform to ISO 1043.
Collective compatibility The tables below show which devices can be connected to the collective detector line of input/output module FDCIO223. Any devices that are neither listed below nor detailed in the 'List of compatibility' are to be regarded as incompatible.
________________ Mode of mounting □ Without housing □ With housing FDCH221 Configuration of input/output 'I/O 1' □ Siemens/Cerberus detector line, SynoLINE600 □ SynoLINE300 detector line □ Contact input □ Control line without confirmation □ Inverted control □ Reverse-polarity monitoring of control Configuration of input/output 'I/O 2' □...
Page 66
Annex Planning the control line Parameters Input/output 'I/O 1' Input/output 'I/O 2' Polarity of control and monitoring □ Same polarity □ Same polarity systems in relation to one another □ Reverse polarity □ Reverse polarity Activation period/behavior □ Permanent □ Permanent □...
Impact Communication, 22 Chemicals, 49 Moisture, 49 DC 24 V voltage Temperature, 49 External fuse, 35 Input/output module FDCIO223 Degraded mode operation Transponder, 5 Collective behavior, 43 Inputs/outputs FDCIO223 Fire control panel failure, 43 Secondary side, 21 Detector exchanger and tester...
Page 68
Adjustment element, 21 Primary side Communication with the control panel via the detector line, 21 Line status display, 19 Status display FDCIO223, 18 Reverse-polarity Line status display Monitoring, 36 LED, 19 List of compatibility, 7, 28, 43, 47, 63, 64...
Page 69