Feeder Protection and Control REF615
Product Guide

Advertisement

Table of Contents
loading

Summary of Contents for ABB REF615

  • Page 1 Power Products Feeder Protection and Control REF615 Product Guide...
  • Page 2: Table Of Contents

    15. Access control ......14 Disclaimer The information in this document is subject to change without notice and should not be construed as a commitment by ABB Oy. ABB Oy assumes no responsibility for any errors that may appear in this document.
  • Page 3: Description

    The IED is also used as back-up protection in applications, where an inde- pendent and redundant protection system is The feeder protection IED REF615 is available required. with six alternative standard configurations. The table below indicates the functions sup- Depending on the preconfiguration made, ported by the different IED configurations.
  • Page 4 Feeder Protection and Control 1MRS756379 D REF615 Product version: 2.0 Functionality Protection Directional earth-fault, low-set stage, • • • • instance 1 Directional earth-fault, low-set stage, • • • • instance 2 • • • • Directional earth-fault, high-set stage Non-directional (cross country) earth-fault, us- •...
  • Page 5 Feeder Protection and Control 1MRS756379 D REF615 Product version: 2.0 Functionality Measurement • • • • • • Transient disturbance recorder • • • • • • Three-phase current • • • • • • Current sequence components Three-phase voltage •...
  • Page 6: Protection Functions

    Feeder Protection and Control 1MRS756379 D REF615 Product version: 2.0 Enhanced with optional hardware and soft- 3. Protection functions ware, the IED also features three light detec- tion channels for arc fault protection of the circuit breaker, busbar and cable compart- The IED offers directional and non-direc- ment of metal-enclosed indoor switchgear.
  • Page 7 Feeder Protection and Control 1MRS756379 D REF615 Product version: 2.0 Fig. 2 Protection function overview of standard configuration C and D Fig. 3 Protection function overview of standard configuration E...
  • Page 8 Feeder Protection and Control 1MRS756379 D REF615 Product version: 2.0 Fig. 4 Protection function overview of standard configuration F...
  • Page 9: Application

    The feeder protection IED REF615 can be residual voltage measurement. The residual supplied either with directional or nondi- current calculated from the phase currents rectional earth-fault protection.
  • Page 10 Feeder Protection and Control 1MRS756379 D REF615 Product version: 2.0 formers. The residual current for the earth- failure supervision for incoming feeders fault protection is derived from the phase with busbar voltage measurement. Standard currents. When applicable, the core-balance configuration F offers in addition to standard...
  • Page 11 Feeder Protection and Control 1MRS756379 D REF615 Product version: 2.0 Fig. 7 Protection and control of two incoming feeders using IEDs with standard configuration F. The two incoming feeders can be connected in parallel by closing the busbar- sectionalizing breaker. To achive selective overcurrent protection, directional overcurrent stages are needed.
  • Page 12: Control

    Feeder Protection and Control 1MRS756379 D REF615 Product version: 2.0 recording function when the measured value 5. Control falls below or exceeds the set values. The binary signal channels can be set to start a recording on the rising or the falling edge of The IED offers control of one circuit breaker the binary signal or both.
  • Page 13: Circuit-Breaker Monitoring

    Feeder Protection and Control 1MRS756379 D REF615 Product version: 2.0 protection blocks, time stamp, etc. The fault software. Any fault or malfunction detected recording can be triggered by the start signal will be used for alerting the operator. A per-...
  • Page 14: Access Control

    Feeder Protection and Control 1MRS756379 D REF615 Product version: 2.0 put is normally used in applications requiring 15. Access control sensitive earth-fault protection and featuring core-balance current transformers. The three phase-voltage inputs and the residual-voltage To protect the IED from unauthorized access...
  • Page 15 Feeder Protection and Control 1MRS756379 D REF615 Product version: 2.0 tion functionality, for example, horizontal DNP3 supports both serial and TCP modes communication between the IEDs, is only for connection to one master. enabled by the IEC 61850 communication protocol.
  • Page 16 Feeder Protection and Control 1MRS756379 D REF615 Product version: 2.0 Table 4. Supported communication interfaces and protocols Interfaces / With optional arc protection Without arc protection Protocols Ethernet Serial Ethernet Serial Serial (RJ-45 or LC) (RS-485) (RJ-45 or LC) (RS-485 /...
  • Page 17: Technical Data

    Feeder Protection and Control 1MRS756379 D REF615 Product version: 2.0 18. Technical data Table 5. Dimensions Description Value Width frame 179.8 mm, case 164 mm Height frame 177 (4U) case 160 mm Depth 194 mm (153 +41 mm) Weight 3.5 kg spare unit 1.8 kg...
  • Page 18 Feeder Protection and Control 1MRS756379 D REF615 Product version: 2.0 Table 7. Energizing inputs Description Value Rated frequency 50/60 Hz ± 5 Hz Current inputs Rated current, I 0.2/1 A 1/5 A Thermal withstand capabil- ity: • Continuously 20 A •...
  • Page 19 Feeder Protection and Control 1MRS756379 D REF615 Product version: 2.0 Table 10. Signal outputs and IRF output Description Value 250 V AC/DC Rated voltage Continuous contact carry Make and carry for 3.0 s 10 A Make and carry 0.5 s...
  • Page 20 Feeder Protection and Control 1MRS756379 D REF615 Product version: 2.0 Table 14. Degree of protection of flush-mounted IED Description Value IP 54 Front side Rear side, connection terminals IP 20 Table 15. Environmental conditions Description Value Operating temperature range -25...+55ºC (continuous) Short-time service temperature range -40...+85ºC (<16h)
  • Page 21 Feeder Protection and Control 1MRS756379 D REF615 Product version: 2.0 (Table continued) Radio frequency interference tests: • Conducted, common mode According to IEC 61000-4-6 IEC 60255-22-6, level 3 10 V (emf), f = 150 kHz...80 MHz • Radiated, amplitude-modulated According to IEC 61000-4-3 and IEC 60255-22-3, level 3 10 V/m (rms), f=80...1000 MHz...
  • Page 22 Feeder Protection and Control 1MRS756379 D REF615 Product version: 2.0 Table 18. Insulation tests Description Value Dielectric tests: According to IEC 60255-5 • Test voltage 2 kV, 50 Hz, 1 min 500 V, 50 Hz, 1min, communication Impulse voltage test: According to IEC 60255-5 •...
  • Page 23 Feeder Protection and Control 1MRS756379 D REF615 Product version: 2.0 Protection functions Table 24. Three-phase non-directional overcurrent protection (PHxPTOC) Operation Depending on the frequency of the current measured: f ±2Hz accuracy PHLPTOC ±1.5% of the set value or ±0.002 x I PHHPTOC ±1.5% of set value or ±0.002 x I...
  • Page 24 Feeder Protection and Control 1MRS756379 D REF615 Product version: 2.0 Table 25. Three-phase non-directional overcurrent protection (PHxPTOC) main settings Parameter Function Value (Range) Step Start value PHLPTOC 0.05...5.00 x I 0.01 PHHPTOC 0.10...40.00 x I 0.01 PHIPTOC 1.00...40.00 x I 0.01...
  • Page 25 Feeder Protection and Control 1MRS756379 D REF615 Product version: 2.0 Table 26. Three-phase directional overcurrent protection (DPHxPDOC) Operation Depending on the frequency of the current/voltage measured: f ±2Hz accuracy DPHLPDOC Current: ±1.5% of the set value or ±0.002 x I Voltage: ±1.5% of the set value or ±0.002 x U...
  • Page 26 Feeder Protection and Control 1MRS756379 D REF615 Product version: 2.0 Table 28. Non-directional EF protection (EFxPTOC) Operation Depending on the frequency of the current measured: f ±2Hz accuracy EFLPTOC ±1.5% of the set value or ±0.002 x I EFHPTOC ±1.5% of set value or ±0.002 x I (at currents in the range of 0.1…10 x I...
  • Page 27 Feeder Protection and Control 1MRS756379 D REF615 Product version: 2.0 Table 30. Directional EF protection (DEFxPDEF) Operation Depending on the frequency of the current measured: f ±2Hz accuracy Current: DEFLPDEF ±1.5% of the set value or ±0.002 x I Voltage: ±1.5% of the set value or ±0.002 x U...
  • Page 28 Feeder Protection and Control 1MRS756379 D REF615 Product version: 2.0 Table 31. Directional EF protection (DEFxPDEF) main settings Parameter Function Value (Range) Step Start value DEFLPDEF 0.010...5.000 x I 0.005 DEFHPDEF 0.10...40.00 x I 0.01 Directional mode DEFLPDEF 1=Non-directional 2=Forward...
  • Page 29 Feeder Protection and Control 1MRS756379 D REF615 Product version: 2.0 Table 34. Three-phase overvoltage protection (PHPTOV) Operation Depending on the frequency of the voltage measured: f ±2Hz accuracy ±1.5% of the set value or ±0.002 x U Start time 1) 2)
  • Page 30 Feeder Protection and Control 1MRS756379 D REF615 Product version: 2.0 Table 36. Three-phase undervoltage protection (PHPTUV) Operation Depending on the frequency of the voltage measured: f ±2Hz accuracy ±1.5% of the set value or ±0.002 x U Start time 1) 2)
  • Page 31 Feeder Protection and Control 1MRS756379 D REF615 Product version: 2.0 Table 39. Positive sequence undervoltage protection (PSPTUV) main settings Parameter Function Value (Range) Step Start value PSPTUV 0.010...1.200 x U 0.001 Operate delay time PSPTUV 40...120000 ms Voltage block value PSPTUV 0.01...1.0 x U...
  • Page 32 Feeder Protection and Control 1MRS756379 D REF615 Product version: 2.0 Table 42. Residual overvoltage protection (ROVPTOV) Operation Depending on the frequency of the voltage measured: f ±2Hz accuracy ±1.5% of the set value or ±0.002 x U Start time 1) 2)
  • Page 33 Feeder Protection and Control 1MRS756379 D REF615 Product version: 2.0 Table 45. Negative phase-sequence current protection (NSPTOC) main settings Parameter Function Value (Range) Step Start value NSPTOC 0.01...5.00 x I 0.01 Time multiplier NSPTOC 0.05...15.00 0.05 Operate delay time NSPTOC 40...200000 ms...
  • Page 34 Feeder Protection and Control 1MRS756379 D REF615 Product version: 2.0 Table 48. Circuit breaker failure protection (CCBRBRF) Operation accuracy Depending on the frequency of the current measured: fn ±2Hz ±1.5% of the set value or ±0.002 x I Operate time accuracy ±1.0% of the set value or ±20 ms...
  • Page 35 Feeder Protection and Control 1MRS756379 D REF615 Product version: 2.0 (Table continued) Maximum temperature T1PTTR 20.0...200.0°C (temperature level for operate) Alarm value T1PTTR 20.0...150.0°C (Temperature level for start (alarm)) Reclose temperature T1PTTR 20.0...150.0°C (Temperature for reset of block reclose after operate)
  • Page 36 Feeder Protection and Control 1MRS756379 D REF615 Product version: 2.0 Table 55. Arc protection (ARCSARC) main settings Parameter Function Value (Range) Step Phase start value ARCSARC 0.50...40.00 x I 0.01 (Operating phase current) Ground start value ARCSARC 0.05...8.00 x I 0.01...
  • Page 37 Feeder Protection and Control 1MRS756379 D REF615 Product version: 2.0 Measurement functions Table 58. Three-phase current measurement (CMMXU) Operation Depending on the frequency of the current measured: f ±2Hz accuracy ±0.5% or ±0.002 x In (at currents in the range of 0.01...4.00 x In) Suppression of DFT: -50dB at f = n x fn, where n = 2, 3, 4, 5,…...
  • Page 38 Feeder Protection and Control 1MRS756379 D REF615 Product version: 2.0 Table 63. Three-phase power and energy (PEMMXU) Operation At all three currents in range 0.10…1.20 x I accuracy At all three voltages in range 0.50…1.15 x U At the frequency f ±1Hz...
  • Page 39: Display Options

    Feeder Protection and Control 1MRS756379 D REF615 Product version: 2.0 improved information overview. The large 19. Display options display is suited for IED installations where the front panel user interface is frequently used, whereas the small display is suited for...
  • Page 40: Mounting Methods

    Feeder Protection and Control 1MRS756379 D REF615 Product version: 2.0 Panel cut-out for flush mounting: 20. Mounting methods • Height: 161.5±1 mm • Width: 165.5±1 mm By means of appropriate mounting acces- sories the standard IED case for the 615 series IEDs can be flush mounted, semi-flush 21.
  • Page 41: Selection And Ordering Data

    Feeder Protection and Control 1MRS756379 D REF615 Product version: 2.0 string of codes generated from the hardware 22. Selection and and software modules of the IED. ordering data Use the ordering key information in Fig. 10 to generate the order number when ordering The IED type and serial number label identi- complete protection IEDs.
  • Page 42 Feeder Protection and Control 1MRS756379 D REF615 Product version: 2.0 H B F C A C A B N B B 1 A C N 1 X C DESCRIPTION Communication serial RS-485 (incl. IRIG-B) Glass fi bre ST 1) 2)
  • Page 43 Feeder Protection and Control 1MRS756379 D REF615 Product version: 2.0 H B F C A C A B N B B 1 A C N 1 X C DESCRIPTION Language English English and German Front panel Small LCD Large LCD...
  • Page 44: Accessories And Ordering Data

    19 ” rack mounting kit with cutout for one IED 1MRS050694 19 ” rack mounting kit with cutout for two IEDs 1MRS050695 Mounting bracket for REF615 with test switch RTXP in 4U 2RCA022642P0001 Combiflex (RHGT 19” variant C) Mounting bracket for REF615 in 4U Combiflex (RHGT 19”...
  • Page 45 Table 71. Tools Configuration and setting tools Version PCM600 2.0 SP2 or later Web-browser based user interface IE 7.0 or later REF615 Connectivity Package 2.0 or later Table 72. Supported functions Function WebHMI PCM600 IED signal configuration (signal matrix tool) •...
  • Page 46: Supported Abb Solutions

    IEDs. The genuine IEC 61850 implementation and ABB’s Connectivity Package concept enable a MicroSCADA Pro is designed for complete seamless integration of 615 series IEDs with functionality for real-time monitoring and ABB’s Station Automation device COM600...
  • Page 47: Terminal Diagrams

    Feeder Protection and Control 1MRS756379 D REF615 Product version: 2.0 26. Terminal diagrams Fig. 14 Terminal diagram of standard configuration B...
  • Page 48 Feeder Protection and Control 1MRS756379 D REF615 Product version: 2.0 Fig. 15 Terminal diagram of standard configuration D...
  • Page 49 Feeder Protection and Control 1MRS756379 D REF615 Product version: 2.0 Fig. 16 Terminal diagram of standard configuration E and F...
  • Page 50: Certificates

    28. References www.abb.com/substationautomation por- tal offers you information about the distribu- tion automation product and service range. You will find the latest relevant information on the REF615 protection IED on the product page. Fig. 17 Product page...
  • Page 51: Functions, Codes And Symbols

    Feeder Protection and Control 1MRS756379 D REF615 Product version: 2.0 29. Functions, codes and symbols Table 74. REF615 Functions, codes and symbols Functions IEC 61850 ANSI 60617 Protection functions PHLPTOC Three-phase non-directional overcurrent, 3I> 51P-1 low-set stage Three-phase non-directional overcurrent, PHHPTOC 3I>>...
  • Page 52 Feeder Protection and Control 1MRS756379 D REF615 Product version: 2.0 Functions IEC 61850 ANSI 60617 Trip circuit supervision TCSSCBR Circuit-breaker condition monitoring SSCBR CBCM CBCM Disconnector position indication DCSXSWI I <-> O DC I <-> O DC Earthing switch indication ESSXSWI I <->...