5 SETTINGS
The main reception menu is applicable to configurable GOOSE only and contains the configurable GOOSE dataset items
for reception:
PATH: SETTINGS
PRODUCT SETUP
RECEPTION
CONFIGURABLE GOOSE
CONFIG GSE 1
DATASET ITEMS
MESSAGE
MESSAGE
MESSAGE
The configurable GOOSE settings allow the G60 to be configured to receive a number of different datasets within IEC
61850 GOOSE messages. Up to sixteen different configurable datasets can be configured for reception. This is useful for
intercommunication between G60 IEDs and devices from other manufacturers that support IEC 61850.
For intercommunication between G60 IEDs, the fixed (DNA/UserSt) dataset can be used. The DNA/UserSt dataset con-
tains the same DNA and UserSt bit pairs that are included in GSSE messages.
To set up a G60 to receive a configurable GOOSE dataset that contains two IEC 61850 single point status indications, the
following dataset items can be selected (for example, for configurable GOOSE dataset 1): "GGIO3.ST.Ind1.stVal" and
"GGIO3.ST.Ind2.stVal". The G60 will then create a dataset containing these two data items. The Boolean status values
from these data items can be utilized as remote input FlexLogic™ operands. First, the
must be set to contain dataset "GOOSEIn 1" (that is, the first configurable dataset). Then
must be set to "Dataset Item 1" and "Dataset Item 2". These remote input FlexLogic™ operands will then change state in
accordance with the status values of the data items in the configured dataset.
Double-point status values may be included in the GOOSE dataset. Received values are populated in the
GGIO3.ST.IndPos1.stVal and higher items.
Floating point analog values originating from MMXU logical nodes may be included in GOOSE datasets. Deadband (non-
instantaneous) values can be transmitted. Received values are used to populate the GGIO3.MX.AnIn1 and higher items.
Received values are also available as FlexAnalog™ parameters (GOOSE analog In1 and up).
GGIO3.MX.AnIn1 to GGIO3.MX.AnIn32 can only be used once for all sixteen reception datasets.
NOTE
The main menu for the IEC 61850 server configuration is shown below.
PATH: SETTINGS
PRODUCT SETUP
SERVER
CONFIGURATION
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
GE Multilin
COMMUNICATIONS
IEC 61850 PROTOCOL
CONFIGURABLE GOOSE 1(16)
ITEM
1:
GGIO3.ST.Ind1.stVal
ITEM
2:
GGIO3.ST.IndPos1.stV
ITEM
3:
None
ITEM 32:
None
COMMUNICATIONS
IEC 61850 PROTOCOL
IED NAME: IECDevice
LD INST: LDInst
LOCATION: Location
IEC/MMS TCP PORT
NUMBER:
102
INCLUDE NON-IEC
DATA: Enabled
SERVER SCANNING:
Disabled
G60 Generator Protection System
5.2 PRODUCT SETUP
GSSE/GOOSE CONFIGURATION
CONFIG GSE 1(32) DATA ITEMS
Range: all valid MMS data item references for
transmitted data
Range: all valid MMS data item references for
transmitted data
Range: all valid MMS data item references for
transmitted data
Range: all valid MMS data item references for
transmitted data
REMOTE DEVICE 1(16) DATASET
REMOTE IN 1(16) ITEM
SERVER CONFIGURATION
Range: up to 32 alphanumeric characters
Range: up to 32 alphanumeric characters
Range: up to 80 alphanumeric characters
Range: 1 to 65535 in steps of 1
Range: Disabled, Enabled
Range: Disabled, Enabled
5
setting
settings
5-29